BRAND | Edwards |
Product | FHSD8330 |
Internal code | IMP4819603 |
Technical specification | UTC™ Modulaser® High Sensitivity Smoke Detector It is the suction unit, which requires 1 unit FHSD8300 (Head Module without screen) or FHSD8310 (Standard Head Module with TFT screen), for 1 to 8 units of FHSD8330, communicated via RS485, can be connected up to 250 m of sampling pipe per module that draws air from the protected area, analyzes it and determines if a pre-alarm or alarm should be activated. Particle sensitivity range 0.003 to 10 Microns. Measurement range (%OBS/m) 0.0015 to 25%. Four alarm levels (Aux, Pre-alarm, Alarm and Alarm 2). Number of sample points, Up to 20 - Class A, Up to 40 - Class B, Up to 50 - Class C. According to the PipeCAD calculation program. Inlet size 25 0 27 MM. Requires 24V power supply (950 mA). Dimensions: 110.5 x 113.5 x 300 mm. Certificates: CE and CPR (EN54-20). |
Please Contact Us to Order to offer competitive prices and delivery time for Edwards - FHSD8330 number, also you may ask some other model number is well. We can offer competitive price, and delivery time with wide products distribution network in Portugal Industrial products Market.
WE SELL ONLY NEW AND ORIGINAL PRODUCTS!
Our company is not an authorized distributor. All rights are reserved by the manufacturers and their official partners.